An ICA-Based HVAC Load Disaggregation Method Using Smart Meter Data

2022-09-19 · Hyeonjin Kim, Kai Ye, Han Pyo Lee, Rongxing Hu, Ning Lu, Di wu, PJ Rehm

This paper presents an independent component analysis (ICA) based unsupervised-learning method for heat, ventilation, and air-conditioning (HVAC) load disaggregation using low-resolution (e.g., 15 minutes) smart meter data. We first demonstrate that electricity consumption profiles on mild-temperature days can be used to estimate the non-HVAC base load on hot days. A residual load profile can then be calculated by subtracting the mild-day load profile from the hot-day load profile. The residual load profiles are processed using ICA for HVAC load extraction. An optimization-based algorithm is proposed for post-adjustment of the ICA results, considering two bounding factors for enhancing the robustness of the ICA algorithm. First, we use the hourly HVAC energy bounds computed based on the relationship between HVAC load and temperature to remove unrealistic HVAC load spikes. Second, we exploit the dependency between the daily nocturnal and diurnal loads extracted from historical meter data to smooth the base load profile. Pecan Street data with sub-metered HVAC data were used to test and validate the proposed methods.Simulation results demonstrated that the proposed method is computationally efficient and robust across multiple customers.

📄 PDF Abstract BibTeX arXiv:2209.09165

Code (0)

등록된 구현이 없습니다.

Methods 이 논문이 사용한 방법론

Test 설명 없음
ICA _Independent component analysis (ICA) is a statistical and computational technique for revealing hidden factors that underlie sets of random variables, measurements, or…
BASE 설명 없음

Similar Papers 제목 키워드 기반

A Modified Sequence-to-point HVAC Load Disaggregation Algorithm

2022-12-09 · Kai Ye, Hyeonjin Kim, Yi Hu, Ning Lu 외

This paper presents a modified sequence-to-point (S2P) algorithm for disaggregating the heat, ventilation, and air conditioning (HVAC) load from the total building electricity consumption. The original S2P model is convo…

Activity Detection And Modeling Using Smart Meter Data: Concept And Case Studies

2020-10-26 · Hao Wang, Gonzague Henri, Chin-Woo Tan, Ram Rajagopal

Electricity consumed by residential consumers counts for a significant part of global electricity consumption and utility companies can collect high-resolution load data thanks to the widely deployed advanced metering in…

Action DetectionActivity Detection

Federated Sequence-to-Sequence Learning for Load Disaggregation from Unbalanced Low-Resolution Smart Meter Data

2024-08-15 · Xiangrui Li

The importance of Non-Intrusive Load Monitoring (NILM) has been increasingly recognized, given that NILM can enhance energy awareness and provide valuable insights for energy program design. Many existing NILM methods of…

Federated LearningNon-Intrusive Load Monitoring

Unsupervised Disaggregation of Water Heater Load from Smart Meter Data Processing

2021-04-07 · Thierry Zufferey, Gustavo Valverde, Gabriela Hug

In the residential sector, electric water heaters are appliances with a relatively high power consumption and a significant thermal inertia, which is particularly suitable for Demand Response schemes. The success of effi…

Non-Intrusive Load Monitoring

MARTINI: Smart Meter Driven Estimation of HVAC Schedules and Energy Savings Based on WiFi Sensing and Clustering

2021-10-17 · Kingsley Nweye, Zoltan Nagy

HVAC systems account for a significant portion of building energy use. Nighttime setback scheduling is an energy conservation measure where cooling and heating setpoints are increased and decreased respectively during un…