Angular Stability Analysis of Parallel Connected Grid-following PV Inverters
High penetration of distributed generators (DG) in modern power grids creates angle, voltage, and frequency instabilities. Most of the work in the literature has focused on small-signal stability analysis of single grid-connected inverters without thoroughly investigating their transient stability for large disturbances and interactions between parallel-connected inverters. To address these challenges, this paper examines the transient angular stability of a cluster of grid-following current source inverters. In a low inertia weak grid environment, grid-following inverters may lose synchronism due to faults and large-signal disturbances. A comparison of the voltage injection angle for pre-fault, fault-on trajectory, and post-fault conditions is performed, and an evaluation of the critical fault clearing time is directly related to the uniformity of the aggregated grid-following inverters. The results show that some inverters lose synchronism more quickly than others due to considerable variances in line impedances and apparent power values. Additionally, inverters with high apparent power are more susceptible to losing synchronism due to the maximum current limit, causing the voltage at the point of common coupling to decrease.
Code (0)
등록된 구현이 없습니다.
Similar Papers 제목 키워드 기반
Current-Limiting Droop Control Design and Stability Analysis for Paralleled Boost Converters in DC Microgrids
In this brief, a novel current-limiting droop controller for paralleled dc-dc boost converters loaded by constant impedance Z, constant current I, or constant power P loads in a dc microgrid is proposed to guarantee clos…
Autonomous Grid-Forming Inverter Exponential Droop Control for Improved Frequency Stability
This paper introduces the novel Droop-e grid-forming power electronic converter control strategy, which establishes a non-linear, active power--frequency droop relationship based on an exponential function of the power o…
On the Incorporation of Stability Constraints into Sequential Operational Scheduling
With the increasing penetration of Inverter-Based Resources (IBRs), power system stability constraints must be incorporated into the operational framework, transforming it into stability-constrained optimization. Current…
Decision MakingSchedulingPower Control of Converters Connected via an L Filter to a Weak Grid. A Flatness-Based Approach
In this article, a nonlinear strategy based on a flatness approach is used for controlling the instantaneous complex power supplied from the Point of Common Coupling (PCC) to a weak grid. To this end, the strategy introd…
A Framework for Distributed and Compositional Stability Analysis of Power Grids
Operating modern power grids with stability guarantees is admittedly imperative. Classic stability methods are not well-suited for these dynamic systems as they involve centralized gathering of information and computatio…
Privacy Preserving