Interactive Power to Frequency Dynamics Between Grid-Forming Inverters and Synchronous Generators in Power Electronics-Dominated Power Systems
With increased attention on grid-forming inverters as a power system stabilizing device during periods of high shares of inverter-based resource operations, there is a present need for a transparent and rigorous investigation of the inverted and direct power to frequency control capabilities, and associated impacts, of these devices on hybrid systems. Here, analysis of the frequency dynamics of the droop controlled grid-forming inverter and the synchronous generator illuminates the inverted active power-frequency relationship and the frequency response order reduction, forming the basis for novel, non-linear frequency droop control approaches. Device-level electromagnetic transient domain simulations corroborate the order-reduction findings, establish that a properly designed DC-side system has a negligible dynamical impact on active power transfer and will not impede frequency regulation, and confirm the frequency response improvement with non-linear control. Simulations of the 9- and 39-bus test systems validate the order reduction and associated decoupling of the nadir and rate of change of frequency in large networks. The primary system oscillatory mode confirms the correlation between high shares of grid-forming inverters and increased mode frequency and damping; a sharp decrease in damping is observed at shares above 80%, whether by grid-forming device quantity in large networks or rating variations in a small test system. Finally, simulation results on the Hawaiian island of Maui show a trend towards a first order frequency response with a grid-forming inverter, further corroborating the analytic findings and network impacts.
Code (1)
Similar Papers 제목 키워드 기반
On Stability, Ancillary Services, Operation, and Security of Smart Inverters
This paper presents some recent trends in the research of grid-interactive inverters. Particularly, this paper focuses on stability, ancillary services, operation, and security of single and multiple inverters in the mod…
MarketingEquivalence between State-Space Stability Analysis and Generalized Nyquist Criterion with Frequency Dynamics Included
Stability of power electronic converters connected to power grids is commonly assessed by using the impedance criterion. On the contrary, stability of power grids is typically analysed by using network state-space repres…
Grid-forming frequency shaping control
As power systems transit to a state of high renewable penetration, little or no presence of synchronous generators makes the prerequisite of well-regulated frequency for grid-following inverters unrealistic. Thus, there …
Frequency stability of grid-forming power-limiting droop control
In this paper, we analyze power-limiting grid-forming droop control used for grid-connected power converters. Compared to conventional grid-forming droop control, power-limiting droop control explicitly accounts for acti…
A Practical Assessment of the Power Grid Inertia Constant Using PMUs