Location Method for Forced Oscillation Sources Caused by Synchronous Generators
In this article, we present a new methodology to identify if forced oscillation sources are generated in excitation systems or in turbine governors. In this context, we propose to harness the information that the dynamic state estimation (DSE) provide to be able to apply a dissipating energy flow (DEF) method. The measurements that the phasor measurement units (PMUs) provide are used to estimate the internal states of different generators connected to the same bus. Here, it will be considered that the PMU at the point of connection is only capable of measuring the voltage phasor and the total current phasor. Therefore, the current injection of the generator that is causing the FO is an unobservable variable. To overcome this issue, event playback is applied to simulate the model's response and a comparison between the DSE of multiple generators is made. Finally, when the faulty generator is identified, we compute energy functions for the mechanical control loop and for the excitation control loop. The sign and rate of these energies determine the source of the oscillation, allowing that the FO can be located. Simulated signals are used to show that the proposed method provides a systematic methodology for identification and location of power systems forced oscillations than even could be non-stationary signals.
Code (0)
등록된 구현이 없습니다.
Tasks
State EstimationSimilar Papers 제목 키워드 기반
Locate the Source of Resonance-Involved Forced Oscillation in Power Systems Based on Mode Shape Analysis
This paper proposed a new method to locate the source of forced oscillation that involves resonance with natural oscillation modes. The new method is based on comparing the oscillation mode shape of the forced oscillatio…
Forced Oscillation Identification and Filtering from Multi-Channel Time-Frequency Representation
Location of non-stationary forced oscillation (FO) sources can be a challenging task, especially in cases under resonance condition with natural system modes, where the magnitudes of the oscillations could be greater in …
An Online Data-Driven Method to Locate Forced Oscillation Sources from Power Plants Based on Sparse Identification of Nonlinear Dynamics (SINDy)
Forced oscillations may jeopardize the secure operation of power systems. To mitigate forced oscillations, locating the sources is critical. In this paper, leveraging on Sparse Identification of Nonlinear Dynamics (SINDy…
GridSweep Simulation: Measuring Subsynchronous Impedance Spectra of Distribution Feeder
Peaks and troughs in the subsynchronous impedance spectrum of a distribution feeder may be a useful indication of oscillation risk, or more importantly lack of oscillation risk, if inverter-based resource (IBR) deploymen…
A PMU-Based Machine Learning Application for Fast Detection of Forced Oscillations from Wind Farms
Today's evolving power system contains an increasing amount of power electronic interfaced energy sources and loads that require a paradigm shift in utility operations. Sub-synchronous oscillations at frequencies around …
BIG-bench Machine Learning