MIMO Grid Impedance Identification of Three-Phase Power Systems: Parametric vs. Nonparametric Approaches
A fast and accurate grid impedance measurement of three-phase power systems is crucial for online assessment of power system stability and adaptive control of grid-connected converters. Existing grid impedance measurement approaches typically rely on pointwise sinusoidal injections or sequential wideband perturbations to identify a nonparametric grid impedance curve via fast Fourier computations in the frequency domain. This is not only time-consuming, but also inaccurate during time-varying grid conditions, while on top of that, the identified nonparametric model cannot be immediately used for stability analysis or control design. To tackle these problems, we propose to use parametric system identification techniques (e.g., prediction error or subspace methods) to obtain a parametric impedance model directly from time-domain current and voltage data. Our approach relies on injecting wideband excitation signals in the converter's controller and allows to accurately identify the grid impedance in closed loop within one injection and measurement cycle. Even though the underlying parametric system identification techniques are well-studied in general, their utilization in a grid impedance identification setup poses specific challenges, is vastly underexplored, and has not gained adequate attention in urgent and timely power systems applications. To this end, we demonstrate in numerical experiments how the proposed parametric approach can accomplish a significant improvement compared to prevalent nonparametric methods.
Code (0)
등록된 구현이 없습니다.
Tasks
subspace methodsSimilar Papers 제목 키워드 기반
The Impact of Three-phase Impedances on the Stability of DER systems
In this work we explore impedance-based interactions that arise when inverter-connected distributed energy resources (DERs) inject real and reactive power to regulate voltage and power flows on three-phase unbalanced dis…
Impedance Reshaping Method of DFIG System Based on Compensating Rotor Current Dynamic to Eliminate PLL Influence
The phase-locked loop (PLL) used in the doubly fed induction generator (DFIG) can cause frequency coupling phenomena, which will give negative resistance characteristics ofthe DFIG at low frequency, resulting in stabilit…
GridSweep Simulation: Measuring Subsynchronous Impedance Spectra of Distribution Feeder
Peaks and troughs in the subsynchronous impedance spectrum of a distribution feeder may be a useful indication of oscillation risk, or more importantly lack of oscillation risk, if inverter-based resource (IBR) deploymen…
Voltage Support Capability Analysis of Grid-Forming Inverters with Current-Limiting Control Under Asymmetrical Grid Faults
Voltage support capability is critical for grid-forming (GFM) inverters with current-limiting control (CLC) during grid faults. Despite the findings on the voltage support for symmetrical grid faults, its applicability t…
Enhanced Grid Following Inverter (E-GFL): A Unified Control Framework for Stiff and Weak Grids
This paper presents an extensive framework focused on the control design, along with stability and performance analysis, of Grid-Following Inverters (GFL). It aims to ensure their effective operation under both stiff and…