Selection of Optimal Number and Location of PMUs for CNN Based Fault Location and Identification
In this paper, we present a data-driven Forward Selection with Neighborhood Refinement (FSNR) algorithm to determine the number and placement of Phasor Measurement Units (PMUs) for maximizing deep-learning-based fault diagnosis performance. Candidate PMU locations are ranked via a cross-validated Support Vector Machine (SVM) classifier, and each selection is refined through local neighborhood exploration to produce a near-optimal sensor set. The resulting PMU subset is then supplied to a 1D Convolutional Neural Network (CNN) for faulted-line localization and fault-type classification from time-series measurements. Evaluation on modified IEEE 34- and IEEE 123-bus systems demonstrates that the proposed FSNR-SVM method identifies a minimal PMU configuration that achieves the best overall CNN performance, attaining over 96 percent accuracy in fault location and over 99 percent accuracy in fault-type classification on the IEEE 34 system, and approximately 94 percent accuracy in fault location and around 99.8 percent accuracy in fault-type classification on the IEEE 123 system.
Code (0)
등록된 구현이 없습니다.
Tasks
Fault DiagnosisSimilar Papers 제목 키워드 기반
Optimal Positioning of PMUs for Fault Detection and Localization in Active Distribution Networks
This paper considers the problem of fault detection and localization in active distribution networks using PMUs. The proposed algorithm consists in computing a set of weighted least squares state estimates whose results …
Fault DetectionFault localizationFault Detection and Localization in Active Distribution Networks using Optimally Placed Phasor Measurements Units
This paper introduces an algorithm able to detect and localize the occurrance of a fault in an Active Distribution Network, using the measurements collected by Phasor Measurement Units (PMUs). First, a basic algorithm th…
Fault DetectionFault localizationWhich Neural Network to Choose for Post-Fault Localization, Dynamic State Estimation and Optimal Measurement Placement in Power Systems?
We consider a power transmission system monitored with Phasor Measurement Units (PMUs) placed at significant, but not all, nodes of the system. Assuming that a sufficient number of distinct single-line faults, specifical…
Fault localizationState EstimationMulti-Objective PMU Allocation for Resilient Power System Monitoring
Phasor measurement units (PMUs) enable better system monitoring and security enhancement in smart grids. In order to enhance power system resilience against outages and blackouts caused by extreme weather events or man-m…
On PMU Data Integrity under GPS Spoofing Attacks: A Sparse Error Correction Framework
Consider the problem of mitigating the impact on data integrity of phasor measurement units (PMUs) given a GPS spoofing attack. We present a sparse error correction framework to treat PMU measurements that are potentiall…