Self-Adaptive Active Damping Method for Stability Enhancement of Systems With Black-Box Inverters Considering Operating Points
Due to the black-box nature of inverters and the wide variation range of operating points, it is challenging to on-line predict and adaptively enhance the stability of inverter-based systems. To solve this problem, this paper provides a feasible self-adaptive active damping method to eliminate potential small-signal instability of systems with black-box inverters under multiple operating points. First, the framework that includes grid impedance estimation, inverters' admittance identification, and self-adaptive strategy is presented. Second, a widely-applicable and engineering-friendly method for inductive-resistive grid impedance estimation is studied, in which a frequency-integral-based dq-axis aligning method is presented to avoid the inaccuracy resulting from the disturbance theta. Then, to make the system have a sufficient stable margin under different operating points, a self-adaptive active damper (SAD) as well as its control strategy with lag compensator modification is proposed, in which the SAD's damping compensation mechanism for the system's stability enhancement is investigated and revealed. Finally, the mapping between system's parameter variations and SAD's parameters is established based on the artificial neural network (ANN) technique, serving as a computationally light model surrogate that is favorable for on-line parameter-tuning for SAD to compensate the system's damping according to operating points. The effectiveness of the proposed method is verified by simulations in PSACD/EMTDC and experiments in RT-Lab platforms.
Code (0)
등록된 구현이 없습니다.
Similar Papers 제목 키워드 기반
Stability Enhancement of LCL-Type Grid-Following Inverters Using Capacitor Voltage Active Damping
An LCL filter offers superior attenuation for high-frequency harmonics for three-phase grid-following inverters compared to LC and L filters. However, it also introduces an inherent resonance peak, which can lead to powe…
The Effect of Frequency Droop Damping on System Parameters and Battery Sizing During Load Change Condition
Inverter-based resources (IBR) have been widely studied for their advantages on the current power systems. This increase in the penetration of renewable energy has raised some concerns about the stability of the existing…
Influence of Sensor Feedback Limitations on Power Oscillation Damping and Transient Stability
Fundamental sensor feedback limitations for improving rotor angle stability using local frequency or phase angle measurement are derived. Using a two-machine power system model, it is shown that improved damping of inter…
Composite learning backstepping control with guaranteed exponential stability and robustness
Adaptive backstepping control provides a feasible solution to achieve asymptotic tracking for mismatched uncertain nonlinear systems. However, input-to-state stability depends on high-gain feedback generated by nonlinear…
parameter estimationCoordinated control in multi-terminal VSC-HVDC systems to improve transient stability: Impact on electromechanical-oscillation damping
Multi-terminal high-voltage Direct Current technology based on Voltage-Source Converter stations (VSC-MTDC) is expected to be one of the most important contributors to the future of electric power systems. In fact, among…