Voltage Stability of Inverter-Based Systems: Impact of Parameters and Irrelevance of Line Dynamics
This paper investigates voltage stability in inverter-based power systems concerning fold and saddle-node bifurcations. An analytical expression is derived for the sensitivity of the stability margin using the normal vector to the bifurcation hypersurface. Such information enables efficient identification of effective control parameters in mitigating voltage instability. Comprehensive analysis reveals that reactive loading setpoint and current controller's feedforward gain are the most influential parameters for enhancing voltage stability in a grid-following (GFL) inverter system, while the voltage controller's feedforward gain plays a dominant role in a grid-forming (GFM) inverter. Notably, both theoretical and numerical results demonstrate that transmission line dynamics have no impact on fold/saddle-node bifurcations in these systems. Results in this paper provide insights for efficient analysis and control in future inverter-dominated power systems through reductions in parameter space and model complexity.
Code (0)
등록된 구현이 없습니다.
Similar Papers 제목 키워드 기반
Effects of Line Dynamics on Stability Margin to Hopf Bifurcation in Grid-Forming Inverters
This paper studies the parameter sensitivity of grid-forming inverters to Hopf bifurcations to address oscillatory instability. An analytical expression for the sensitivity of the stability margin is derived based on the…
SensitivityThe Effect of Frequency Droop Damping on System Parameters and Battery Sizing During Load Change Condition
Inverter-based resources (IBR) have been widely studied for their advantages on the current power systems. This increase in the penetration of renewable energy has raised some concerns about the stability of the existing…
Network-Independent Incremental Passivity Conditions for Grid-Forming Inverter Control
Grid-forming inverters control the power transfer between the AC and DC sides of an electrical grid while maintaining the frequency and voltage of the AC side. This paper focuses on ensuring large-signal stability of an …
Voltage Stability Constrained Unit Commitment in High IBG-Penetrated Power Systems
With the increasing penetration of renewable energy sources, power system operation has to be adapted to ensure the system stability and security while considering the distinguished feature of the Power Electronics (PE) …
SchedulingVocal Bursts Intensity PredictionGershgorin Disc-based Voltage Stability Regions for DER Siting and Control in Distribution Grids
As a consequence of the transition to distributed and renewable energy systems, some distribution system operators are increasingly concerned about power quality, including steady-state voltage volatility. In this paper,…