A Control Chart Approach to Power System Line Outage Detection Under Transient Dynamics
Online transmission line outage detection over the entire network enables timely corrective action to be taken, which prevents a local event from cascading into a large scale blackout. Line outage detection aims to detect an outage as soon as possible after it happened. Traditional methods either do not consider the transient dynamics following an outage or require a full Phasor Measurement Unit (PMU) deployment. Using voltage phase angle data collected from a limited number of PMUs, we propose a real-time dynamic outage detection scheme based on alternating current (AC) power flow model and statistical change detection theory. The proposed method can capture system dynamics since it retains the time-variant and nonlinear nature of the power system. The method is computationally efficient and scales to large and realistic networks. Extensive simulation studies on IEEE 39-bus and 2383-bus systems demonstrated the effectiveness of the proposed method.
Code (0)
등록된 구현이 없습니다.
Tasks
Change DetectionSimilar Papers 제목 키워드 기반
LASSO-Based Multiple-Line Outage Identification In Partially Observable Power Systems
Phasor measurement units (PMUs) create ample real-time monitoring opportunities for modern power systems. Among them, line outage detection and identification remains a crucial but challenging task. Current works on outa…
Line Failure Localization of Power Networks Part II: Cut Set Outages
Transmission line failure in power systems prop-agate non-locally, making the control of the resulting outages extremely difficult. In Part II of this paper, we continue the study of line failure localizability in transm…
Joint Estimation of Operational Topology and Outages for Unbalanced Power Distribution Systems
An electric power distribution system is operated in several distinct radial topologies by opening and closing of system's sectionalizing and tie switches. The estimation of the system's current operational topology is a…
Optimal Phasor Measurement Unit Placement Using a Honey Bee Mating Optimization (HBMO) Technique Considering Measurement Loss and Line Outages
Phasor measurement units (PMUs) are important devices for protection, monitoring, and control of modern power systems. Unlike the supervisory control and data acquisition (SCADA) system which only measure the magnitude, …
Outage Probability of Millimeter Wave Cellular Uplink with Truncated Power Control
In this paper, using the stochastic geometry, we develop a tractable uplink modeling framework for the outage probability of both the single and multi-tier millimeter wave (mmWave) cellular networks. Each tier's mmWave b…