A Pure Integral-Type PLL with a Damping Branch to Enhance the Stability of Grid-Tied Inverter under Weak Grids
In a phase-locked loop (PLL) synchronized inverter, due to the strong nonlinear coupling between the PLL's parame-ters and the operation power angle, the equivalent damping coefficient will quickly deteriorate while the power angle is close to 90{\deg} under an ultra-weak grid, which causes the synchronous instability. To address this issue, in this letter, a pure integral-type phase-locked loop (IPLL) with a damping branch is proposed to replace the traditional PI-type PLL. The equivalent damping coefficient of an IPLL-synchronized inverter is decoupled with the steady-state power angle. As a result, the IPLL-synchronized inverter can stably operate under an ultra-weak grid when the equilibrium point exists. Finally, time-domain simulation results verify the effectiveness and correctness of the proposed IPLL.
Code (0)
등록된 구현이 없습니다.
Similar Papers 제목 키워드 기반
New perspectives on transient stability between grid-following and grid-forming VSCs
The grid-following and grid-forming controls in voltage-source converters are considered as different operation modes and the synchronization mechanism of them are studied separately. In this article, the intrinsic relat…
Self-Adaptive Active Damping Method for Stability Enhancement of Systems With Black-Box Inverters Considering Operating Points
Due to the black-box nature of inverters and the wide variation range of operating points, it is challenging to on-line predict and adaptively enhance the stability of inverter-based systems. To solve this problem, this …
A Sensorised Lattice Footplate for a Semi-Active Prosthetic Foot
This paper investigates whether magnetic plantar sensing can be embedded directly inside the load-bearing compliant element of a low-cost semi-active prosthetic foot. We present a prototype integrating a sensorised 3D-pr…
Stability Enhancement of LCL-Type Grid-Following Inverters Using Capacitor Voltage Active Damping
An LCL filter offers superior attenuation for high-frequency harmonics for three-phase grid-following inverters compared to LC and L filters. However, it also introduces an inherent resonance peak, which can lead to powe…
Measurement-Based Estimation of System State Matrix for AC Power Systems with Integrated VSCs
In this paper, a wide-area measurement system (WAMS)-based method is proposed to estimate the system state matrix for AC system with integrated voltage source converters (VSCs) and identify the electromechanical modes. T…