Data Center Cooling System Optimization Using Offline Reinforcement Learning
The recent advances in information technology and artificial intelligence have fueled a rapid expansion of the data center (DC) industry worldwide, accompanied by an immense appetite for electricity to power the DCs. In a typical DC, around 30~40% of the energy is spent on the cooling system rather than on computer servers, posing a pressing need for developing new energy-saving optimization technologies for DC cooling systems. However, optimizing such real-world industrial systems faces numerous challenges, including but not limited to a lack of reliable simulation environments, limited historical data, and stringent safety and control robustness requirements. In this work, we present a novel physics-informed offline reinforcement learning (RL) framework for energy efficiency optimization of DC cooling systems. The proposed framework models the complex dynamical patterns and physical dependencies inside a server room using a purposely designed graph neural network architecture that is compliant with the fundamental time-reversal symmetry. Because of its well-behaved and generalizable state-action representations, the model enables sample-efficient and robust latent space offline policy learning using limited real-world operational data. Our framework has been successfully deployed and verified in a large-scale production DC for closed-loop control of its air-cooling units (ACUs). We conducted a total of 2000 hours of short and long-term experiments in the production DC environment. The results show that our method achieves 14~21% energy savings in the DC cooling system, without any violation of the safety or operational constraints. Our results have demonstrated the significant potential of offline RL in solving a broad range of data-limited, safety-critical real-world industrial control problems.
Code (0)
등록된 구현이 없습니다.
Tasks
Graph Neural NetworkOffline RLreinforcement-learningReinforcement LearningReinforcement Learning (RL)Methods 이 논문이 사용한 방법론
Similar Papers 제목 키워드 기반
Transforming Cooling Optimization for Green Data Center via Deep Reinforcement Learning
Cooling system plays a critical role in a modern data center (DC). Developing an optimal control policy for DC cooling system is a challenging task. The prevailing approaches often rely on approximating system models tha…
Deep Reinforcement LearningManagementreinforcement-learningReinforcement Learning+1LC-Opt: Benchmarking Reinforcement Learning and Agentic AI for End-to-End Liquid Cooling Optimization in Data Centers
Liquid cooling is critical for thermal management in high-density data centers with the rising AI workloads. However, machine learning-based controllers are essential to unlock greater energy efficiency and reliability, …
Reinforcement LearningControlling Commercial Cooling Systems Using Reinforcement Learning
This paper is a technical overview of DeepMind and Google's recent work on reinforcement learning for controlling commercial cooling systems. Building on expertise that began with cooling Google's data centers more effic…
Managementreinforcement-learningReinforcement LearningReinforcement Learning (RL)Linearized Data Center Workload and Cooling Management
With the current high levels of energy consumption of data centers, reducing power consumption by even a small percentage is beneficial. We propose a framework for thermal-aware workload distribution in a data center to …
ManagementHeuristics and Metaheuristics for Dynamic Management of Computing and Cooling Energy in Cloud Data Centers
Data centers handle impressive high figures in terms of energy consumption, and the growing popularity of Cloud applications is intensifying their computational demand. Moreover, the cooling needed to keep the servers wi…
Management