paper-with-me

홈 › Papers

Fisher Matrix Based Fault Detection for PMUs Data in Power Grids

2022-08-09 · Ke Chen, Dandan Jiang, Bo wang, Hongxia Wang

Abnormal event detection is critical in the safe operation of power system. In this paper, using the data collected from phasor measurement units (PMUs), two methods based on Fisher random matrix are proposed to detect faults in power grids. Firstly, the fault detection matrix is constructed and the event detection problem is reformatted as a two-sample covariance matrices test problem. Secondly, the central limit theorem for the linear spectral statistic of the Fisher matrix is derived and a test statistic for testing faults is proposed. To save computing resources, the screening step of fault interval based on the test statistic is designed to check the existence of faults. Then two point-by-point methods are proposed to determine the time of the fault in the interval. One method detects faults by checking whether the largest sample eigenvalue falls outside the supporting set of limiting spectral distribution of the standard Fisher matrix, which can detect the faults with higher accuracy. The other method tests the faults based on the statistic proposed, which has a faster detection speed. Compared with existing works, the simulation results illustrate that two methods proposed in this paper cost less computational time and provide a higher degree of accuracy.

📄 PDF Abstract BibTeX arXiv:2208.04637

Code (0)

등록된 구현이 없습니다.

Tasks

Event DetectionFault Detection

Methods 이 논문이 사용한 방법론

Test 설명 없음

Similar Papers 제목 키워드 기반

Optimal Positioning of PMUs for Fault Detection and Localization in Active Distribution Networks

2021-04-15 · F. Conte, B. Gabriele, G. -P. Schiapparelli, F. Silvestro 외

This paper considers the problem of fault detection and localization in active distribution networks using PMUs. The proposed algorithm consists in computing a set of weighted least squares state estimates whose results …

Fault DetectionFault localization

Fault Detection and Localization in Active Distribution Networks using Optimally Placed Phasor Measurements Units

2022-04-12 · Francesco Conte, Fabio D'Agostino, Bruno Gabriele, Giacomo-Piero Schiapparelli 외

This paper introduces an algorithm able to detect and localize the occurrance of a fault in an Active Distribution Network, using the measurements collected by Phasor Measurement Units (PMUs). First, a basic algorithm th…

Fault DetectionFault localization

Early Anomaly Detection in Power Systems Based on Random Matrix Theory

2019-07-21

It is important for detecting the anomaly in power systems before it expands and causes serious faults such as power failures or system blackout. With the deployments of phasor measurement units (PMUs), massive amounts o…

Anomaly Detection

Selection of Optimal Number and Location of PMUs for CNN Based Fault Location and Identification

2025-09-02 · Khalid Daud Khattak, Muhammad A. Choudhry arxiv

In this paper, we present a data-driven Forward Selection with Neighborhood Refinement (FSNR) algorithm to determine the number and placement of Phasor Measurement Units (PMUs) for maximizing deep-learning-based fault di…

Fault Diagnosis

Which Neural Network to Choose for Post-Fault Localization, Dynamic State Estimation and Optimal Measurement Placement in Power Systems?

2021-04-07 · Andrei Afonin, Michael Chertkov

We consider a power transmission system monitored with Phasor Measurement Units (PMUs) placed at significant, but not all, nodes of the system. Assuming that a sufficient number of distinct single-line faults, specifical…

Fault localizationState Estimation